Electrical fluting shows as a washboard pattern on the raceways, frosted grey tracks, microcraters under magnification and grey-to-black metallic grease; regreasing cannot stop it, because the cause is VFD-induced bearing current.
The three countermeasures do different jobs: coated and hybrid bearings break the current path through the bearing, while shaft grounding rings divert shaft current to earth and, per IEC 60034-25 as quoted by SKF, are combined with insulated bearings depending on frame size and power.
Check your frame size, coating withstand class and earthing continuity before ordering.
Confirm it is electrical fluting before you spend money on grease
Open a removed bearing and look at the raceways. Electrical fluting appears as a regular wave-like 'washboard' pattern with frosted grey tracks; under magnification you see thousands of tiny microcraters — EDM pits left by each discharge — and the grease typically darkens16,19.
The damage is cumulative: as discharges pile up, premature wear shows up as rising noise and vibration, and failure can arrive within a few months on a motor whose duty profile implies five years or more of bearing life27. The mechanism sits upstream of the bearing.
A PWM drive's common-mode voltage and steep voltage edges drive parasitic high-frequency currents — circulating, shaft-grounding and capacitive discharge . And each discharge through the rolling contact acts like electric-discharge machining, eroding metal between balls and races2,27.
That is why the failure follows the electrical circuit, not the lubrication schedule: changing grease type or regreasing more often will not prevent electrical erosion. So treat correct-lubrication fluting on a VFD motor as an electrical problem17.
Distinguish it from its lookalikes: true brinelling leaves evenly spaced dents at rolling-element pitch, caused by static overload or shock and impact, while fretting leaves reddish-black oxide or shallow depressions at the same spacing — neither shows the regular transverse ridges of fluting16.
If you are planning a replacement, the Bearing Replacement page covers the practical steps; the countermeasure choice comes next.
Place your motor in a frame-size band to know which current you must stop
Which countermeasure can work depends on which bearing current dominates, and that follows motor size. Per ABB, large motors of IEC 280 / NEMA 440 frame and above suffer circulating inductive currents, and their stated solution is to break the current path with one insulated bearing27.
Any VFD-driven motor is at risk from capacitive discharge currents, which pass through the bearing as EDM2,17. IEC 60034-25, as quoted by SKF, ranks the most effective countermeasures by frame: for smaller frame sizes, two insulated bearings plus a brush.
For larger machines, two insulated bearings, an insulated coupling and a brush2.
The countermeasures are complementary rather than either/or: SKF notes a shaft grounding ring diverts current from the shaft via brushes to the housing and ground, and may need to be used in combination with INSOCOAT or hybrid bearings depending on motor power and application2.
One supplier advises both combined for motors above about 100 hp, where discharge and circulating currents are both present17. One check settles more than the bearing choice: after any motor repair, verify earthing continuity.
In one documented pulp-mill case, insulated bearings still failed within 1–2 months because the earthing cable had been left disconnected, and the failures stopped once earthing was restored19.
Shortlisting coated bearings, hybrid ceramics and grounding rings
The three options are not substitutes; they act at different points in the current path. Coated and hybrid bearings both interrupt current through the bearing itself, while a grounding ring gives the shaft current a low-impedance route to earth and so protects the whole machine beyond the bearings2,17.
Use the table to shortlist, then confirm power level against the frame-size guidance above.
| Option | How it protects | Limits / watch-outs |
|---|---|---|
| Insulated coated bearing | Aluminium-oxide coating on a ring surface breaks the current path | Protects only that bearing; coating has a stated withstand voltage to respect |
| Hybrid ceramic bearing | Non-conductive silicon nitride rolling elements block current in AC and DC machines | Highlighted by SKF especially for high-frequency converter duty; only the bearing is protected |
| Shaft grounding ring | Diverts shaft current to ground via brushes, protecting the machine beyond the bearings | Per SKF, may need combining with INSOCOAT or hybrid bearings depending on power and application |
| Combination | Breaks the bearing path and diverts shaft current at the same time | Advised above ~100 hp where discharge and circulating currents coexist |
Specifying a coated bearing: withstand class and mounting care
An INSOCOAT bearing is a standard bearing with the outer surfaces of one ring plasma-sprayed with aluminium oxide and sealed with resin against moisture. SKF's basic coating withstands 1,000 V DC and is 100% tested at that voltage.
Higher variants reach 2,000 V DC and 3,000 V DC, with minimum insulation resistance of 50 MΩ for the standard grade and 150 MΩ for the higher grades3.
Lab tests show breakdown above 3,000 V DC on the basic coating, so pick the variant against the shaft voltages your drive produces rather than defaulting to the cheapest3. Mounting is where coated bearings get damaged.
SKF states they mount like standard bearings for fits, lubrication and maintenance. But the coating must survive the process: induction-heater vibration must not damage the layer, coated inner-ring versions (VL2071) need a protective sleeve or plastic support block.
And SKF recommends a steel spacer ring between the bearing and any preload springs or locknuts3. Write the withstand class and mounting precautions into the order, and ask the supplier how coating condition can be verified in service — the sources carry no coating wear or degradation rate over time.
Judging whether a hybrid ceramic bearing suits your drive
Hybrid bearings keep steel rings and use bearing-grade silicon nitride rolling elements. Because the ceramic is an excellent electrical insulator, SKF states these bearings insulate housing from shaft in AC and DC machines and are highlighted especially for high-frequency converter applications4.
SKF also reports higher speed capability and longer service life than same-sized all-steel bearings under the same operating conditions4. Treat the stronger marketing numbers with care.
The claim that hybrid ceramics are 'the default choice for VFD-driven motors above 100 kW' comes from a single source page and is not independently confirmed in this evidence set.
A supplier page attributes that speed advantage to the ceramic elements weighing 60% less than same-size steel balls, and reports hybrids running 30–50% faster than steel equivalents before load limits — vendor-tier figures you should verify against the specific designation, not quote as class rules23.
What the sources do not give you: numerical resistivity of Si3N4, load and speed rating deltas against a named all-steel bearing, the price premium, or lead times. Ask bidders to state these against your exact designation.
Before you order: retrofit and combination checks
Grounding rings are the retrofit-friendly option: SKF's TKGR kits are designed to fit existing IEC frame motors without major endcap redesign2. Whether a ring alone is enough depends on your power level and which currents are present, so run these checks before the RFQ.
Whether your cable length, switching frequency or reflected-wave dv/dt calls for a common-mode choke or a dV/dt filter alongside the bearing countermeasure is not covered by these sources — put that question to the drive vendor.
The sources also give no life-cycle cost comparison, replacement interval or downtime data for any countermeasure — ask bidders to quote those.
- ✓Confirm the motor frame size and power rating against the IEC 60034-25 countermeasure sets quoted by SKF
- ✓Above ~100 hp with both discharge and circulating currents, plan the ring plus insulated or hybrid bearing together
- ✓Check endcap space and shaft end access for fitting a grounding ring and its mounting brackets
- ✓If specifying coated bearings, note the coating variant, withstand voltage and the mounting sleeves or spacers needed
- ✓Verify earthing continuity — including after any motor repair — since insulated bearings alone failed when earthing was lost in one documented case
- ✓Verify VFD grounding and shielded motor cable installation per IEC TS 60034-25
- ✓Ask each bidder for ring current capacity and brush maintenance requirements; the sources do not publish these figures
Where the sources disagree about IEC 60034-25
Two vendor pages put a power threshold on a grounding-ring requirement, while SKF — the only manufacturer-tier quotation of the standard in this set — gives frame-size-based countermeasure lists and mentions no such mandate. Before you cite the standard in a specification, verify the clause against the standard text itself.
| IEC 60034-25 prescription / threshold (framing) | One source reports | Another reports | What the buyer should do |
|---|---|---|---|
| Countermeasure set for frame size | 2 insulated bearings + brush (small frames); + insulated coupling (large machines) | Ring + insulated bearing combined above 100 hp | Ask which applies to your frame; verify wording against the standard text |
| Grounding-ring mandate threshold | Mandates grounding rings for motors >100 kW | No mandate quoted in SKF's citation of the standard | Do not cite a kW mandate until confirmed against the standard |
Before you request a quote
- The evidence leaves this open — put it to the supplier: no source provides validated shaft-voltage measurement thresholds or vibration-signature details for confirming a fluting diagnosis; ask your condition-monitoring provider what criteria they apply.
- The evidence leaves this open — put it to the supplier: the actual IEC 60034-25 / TS 60034-17 / 60034-18 text and the clause-level mapping of mitigation to frame size and inverter type are not established here; check the standard directly before citing it.
- Confirm named service coverage, response expectations and warranty terms for your destination.
- Request a written quote with price basis, MOQ, tooling, payment terms and production lead time.
- Request the complete specification sheet with units, test conditions and configuration assumptions.
- The evidence leaves this open — put it to the supplier: cable length and reflected-wave dv/dt guidance, and common-mode chokes or dV/dt filters as alternatives, are not covered by these sources.
- The evidence leaves this open — put it to the supplier: no life-cycle cost comparison, replacement intervals, downtime or lead-time data for the countermeasure options.
Sources · 9
- 2cdn.skfmediahub.skf.comManufacturer technical documentation
- 8flowmachinery.comUnclassified source2026-02
- 13iskbearing.comManufacturer technical documentation2026-08
- 16mechcodex.comUnclassified source2026-10
- 17reliabilitysolutions.netUnclassified source2026-08
- 18bearingsindustry.comUnclassified source
- 19maximomastery.comUnclassified source
- 23talosbearing.comUnclassified source2026-08
- 27new.abb.comUnclassified source
Technical references cited for verifiability — not supplier recommendations.Browse the research library.